50 kW

Descarga de Documentos Técnicos
Ficha Técnica
Plano

 Gen Set model number
GSJD10050M
Mechanical power
50 kW
kWe Standby range
50 kW
Engine manufacturer
JOHN DEERE
Engine model number
4045TF150
EPA / Tier
1
Number of cylinders
4
Disp. cu. in. (L)
276(4.5)
Aspiration
Turbocharged
BMEP psi (kpa)
160(1105)
Engine CFM cfm (m^3/min)
187(5.3)
Engine rated Hp (kWm)
100(75)
RPM
1800
Alternator manufacturer
MARATHON
Alternator model number
361PSL1600
Insulation system class
150 H
Voltage
220/440/208/480V
Voltage configuration
PARALLE LOW WYE
Frequency (Hz)
60
Number of phases
3
Standby circuit breaker rating
164.2
82.1
173.7
75.3
 
 Generator's ratings for 150°C H Rise
Standby kW
47
Amps
154
77
163
71
 
 Engine ratings
Standby kW
74
Standby Amps
243
122
257
111
Prime kW
67
Prime Amps
220
110
233
101

 
   

 

   

 
     