  Untitled Document

125 kW

Descarga de Documentos Técnicos
Ficha Técnica
Plano

 Gen Set model number
GSJD10125M
Mechanical power
125
kWe Standby range
122-128
Engine manufacturer
JOHN DEERE
Engine model number
6068TF250
EPA / Tier
1
Number of cylinders
6
Disp. cu. in. (L)
414(6.8)
Aspiration
Turbocharged
BMEP psi (kpa)
202(1395)
Engine CFM cfm (m^3/min)
325(9.2)
Engine rated Hp (kWm)
190(142)
RPM
1800
Alternator manufacturer
MARATHON
Alternator model number
363PSL1607
Insulation system class
150 H
Voltage
220/440/208/480V
Voltage configuration
PARALLE LOW WYE
Frequency (Hz)
60
Number of phases
3
Standby circuit breaker rating
410.5
205.3
434.2
188.2
 
 Generator's ratings for 150°C H Rise
Standby kW
140
Amps
460
230
486
211
 
 Engine ratings
Standby kW
142
Standby Amps
466.4
233
493
214
Prime kW
128
Prime Amps
420.4
210
445
193

 
   

 

   

 
     