3000 kW

Descarga de Documentos Técnicos
Ficha Técnica
Plano

 Gen Set model number
GSDD13000M
Mechanical power
3000
kWe Standby range
3000
Engine manufacturer
DETROIT DIESEL
Engine model number
20V4000G82
EPA / Tier
1
Number of cylinders
20
Disp. cu. in. (L)
5478(89.8)
Aspiration
Turbocharged
BMEP psi (kpa)
323.3(2230)
Engine CFM cfm (m^3/min)
8263.7(234)
Engine rated Hp (kWm)
4036.4(3010)
RPM
1800
Alternator manufacturer
MARATHON
Alternator model number
1030FDM1204
Insulation system class
150 H
Voltage
4160/13800
Voltage configuration
PARALLE LOW WYE
Frequency (Hz)
60
Number of phases
3
Standby circuit breaker rating
4515.9
521.1
164.2
 
 Generator's ratings for 150°C H Rise
Standby kW
3000
Amps
-
521
157
-
 
 Engine ratings
Standby kW
3010
Standby Amps
-
523
158
-
Prime kW
2740
Prime Amps
4,125
476
150
-

 
   

 

   

 
     