logo Distribuidor Autorizado:
emerson
liebert
Mission Critical Care...Experts in Critical Facilities Infrastructure Design & Construction
menuoficinastelefonos
  Untitled Document

2000 kW

Descarga de Documentos Técnicos
Ficha Técnica
Plano

 Gen Set model number
GSDD22000MU
Mechanical power
2000
kWe Standby range
Engine manufacturer
DETROIT DIESEL
Engine model number
16V4000G43
EPA / Tier
2
Number of cylinders
16
Disp. cu. in. (L)
4656(76.3)
Aspiration
Turbocharged
BMEP psi (kpa)
288.6(1990)
Engine CFM cfm (m^3/min)
6356.6(180)
Engine rated Hp (kWm)
3056(2280)
RPM
1800
Alternator manufacturer
MARATHON
Alternator model number
744RSL4056
Insulation system class
150 H
Voltage
380/416/480V
Voltage configuration
WYE
Frequency (Hz)
60
Number of phases
3
Standby circuit breaker rating
3802.9
3473.8
3010.6
-
 
 Generator's ratings for 150°C H Rise
Standby kW
2100
Amps
3.993
3.647
3.161
-
 
 Engine ratings
Standby kW
2280
Standby Amps
3.432
396
125
-
Prime kW
2020
Prime Amps
3.041
351
111
-

 
   

 

   

 
     
  (c)2009 constantino garcia azuara