logo Distribuidor Autorizado:
emerson
liebert
Mission Critical Care...Experts in Critical Facilities Infrastructure Design & Construction
menuoficinastelefonos
  Untitled Document

2000 kW

Descarga de Documentos Técnicos
Ficha Técnica
Plano

 Gen Set model number
GSDD12000M
Mechanical power
2000
kWe Standby range
2000
Engine manufacturer
DETROIT DIESEL
Engine model number
16V4000G81
EPA / Tier
1
Number of cylinders
16
Disp. cu. in. (L)
3965(65)
Aspiration
Turbocharged
BMEP psi (kpa)
326.2(2250)
Engine CFM cfm (m^3/min)
6144.8(174)
Engine rated Hp (kWm)
2936.8(2190)
RPM
1800
Alternator manufacturer
MARATHON
Alternator model number
744RSL4056
Insulation system class
150 H
Voltage
480/4160/13200
Voltage configuration
PARALLE LOW WYE
Frequency (Hz)
60
Number of phases
3
Standby circuit breaker rating
3010.6
347.4
109.5
-
 
 Generator's ratings for 150°C H Rise
Standby kW
2100
Amps
3,161
365
115
3,161
 
 Engine ratings
Standby kW
2190
Standby Amps
3,297
380
120
-
Prime kW
1990
Prime Amps
2,996
346
109
-

 
   

 

   

 
     
  (c)2009 constantino garcia azuara